The adequacy of a Grounding System (GS) to the safety conditions has to be periodically tested by measurements. The test methods and techniques used to verify the electrical characteristics of the GS include the measurements of step and touch voltages. The goal of the test is to verify that touch voltage and step voltage remain below a safe value in all the zones of the installation. The measurements can present some operational difficulties. The purpose of this paper is to present the procedure, step-by-step, of a practical method of measuring touch/step voltages in grounding systems located in urban or industrial areas with reduced accessibility. The suggested method uses auxiliary current electrodes located at short distances. This paper demonstrates by test measurements done in a real case that the method provides conservative results.

A Practical Method to Test the Safety of HV/MV Substation Grounding System / Parise, G.; Martirano, L.; Parise, L.; Tummolillo, F.; Vagnati, G.; Barresi, A.; Cafaro, G.; Colella, Pietro; Di Silvestre, M. L.; Montegiglio, P.; Morozova, E.; Napoli, Roberto; Pons, Enrico; Riva Sanseverino, E.; Sassoli, S.; Tommasini, Riccardo; Torelli, F.; Valtorta, G.; Zizzo, G.. - CD-ROM. - (2015), pp. 502-506. (Intervento presentato al convegno 2015 IEEE 15th International Conference on Environment and Electrical Engineering tenutosi a Roma nel June 10-13, 2015) [10.1109/EEEIC.2015.7165213].

A Practical Method to Test the Safety of HV/MV Substation Grounding System

COLELLA, PIETRO;NAPOLI, Roberto;PONS, ENRICO;TOMMASINI, Riccardo;
2015

Abstract

The adequacy of a Grounding System (GS) to the safety conditions has to be periodically tested by measurements. The test methods and techniques used to verify the electrical characteristics of the GS include the measurements of step and touch voltages. The goal of the test is to verify that touch voltage and step voltage remain below a safe value in all the zones of the installation. The measurements can present some operational difficulties. The purpose of this paper is to present the procedure, step-by-step, of a practical method of measuring touch/step voltages in grounding systems located in urban or industrial areas with reduced accessibility. The suggested method uses auxiliary current electrodes located at short distances. This paper demonstrates by test measurements done in a real case that the method provides conservative results.
2015
9781479979929
File in questo prodotto:
File Dimensione Formato  
paper_post_print_def.pdf

accesso aperto

Descrizione: Articolo
Tipologia: 2. Post-print / Author's Accepted Manuscript
Licenza: Pubblico - Tutti i diritti riservati
Dimensione 311.63 kB
Formato Adobe PDF
311.63 kB Adobe PDF Visualizza/Apri
07165213.pdf

accesso riservato

Descrizione: Articolo versione editoriale
Tipologia: 2a Post-print versione editoriale / Version of Record
Licenza: Non Pubblico - Accesso privato/ristretto
Dimensione 413.49 kB
Formato Adobe PDF
413.49 kB Adobe PDF   Visualizza/Apri   Richiedi una copia
Pubblicazioni consigliate

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11583/2611958