Virtual synchronous machines (VSMs) are a promising technology to integrate distributed energy sources and storage into power grids. The VSM is a power converter that emulates the behavior of a synchronous machine, providing grid services which are necessary to operate a power system in a stable manner. When more VSMs are connected to the same grid, sub-synchronous oscillations between them (and between VSMs and other generators) may occur if damping coefficients and inertias are not properly tuned. For this purpose, virtual friction (VF) has been proposed to provide high damping without a strong coupling of frequency deviation and power output, unlike for frequency droop. VF applies a damping torque to the virtual rotor of the VSMs, proportional to the deviation of the rotor frequency from the center of inertia (COI)-frequency of the grid. To the best of the authors' knowledge, this technique has only been validated theoretically and in simulations for isolated microgrids. The goal of this paper is to demonstrate the effectiveness of VF both in isolated microgrids and in grid connected operation by experiments on a 45kVA setup and their theoretical assessment.
Virtual Friction: Experimental Validation in a Microgrid of 3 Virtual Synchronous Machines / Reissner, Florian; Mallemaci, Vincenzo; Mandrile, Fabio; Bojoi, Radu; Weiss, George. - ELETTRONICO. - (2022), pp. 1-6. (Intervento presentato al convegno 2022 IEEE 23rd Workshop on Control and Modeling for Power Electronics (COMPEL) tenutosi a Tel Aviv, Israel nel 20-23 June 2022) [10.1109/COMPEL53829.2022.9830008].
Virtual Friction: Experimental Validation in a Microgrid of 3 Virtual Synchronous Machines
Mallemaci, Vincenzo;Mandrile, Fabio;Bojoi, Radu;
2022
Abstract
Virtual synchronous machines (VSMs) are a promising technology to integrate distributed energy sources and storage into power grids. The VSM is a power converter that emulates the behavior of a synchronous machine, providing grid services which are necessary to operate a power system in a stable manner. When more VSMs are connected to the same grid, sub-synchronous oscillations between them (and between VSMs and other generators) may occur if damping coefficients and inertias are not properly tuned. For this purpose, virtual friction (VF) has been proposed to provide high damping without a strong coupling of frequency deviation and power output, unlike for frequency droop. VF applies a damping torque to the virtual rotor of the VSMs, proportional to the deviation of the rotor frequency from the center of inertia (COI)-frequency of the grid. To the best of the authors' knowledge, this technique has only been validated theoretically and in simulations for isolated microgrids. The goal of this paper is to demonstrate the effectiveness of VF both in isolated microgrids and in grid connected operation by experiments on a 45kVA setup and their theoretical assessment.File | Dimensione | Formato | |
---|---|---|---|
Virtual_Friction_Experimental_Validation_in_a_Microgrid_of_3_Virtual_Synchronous_Machines.pdf
accesso riservato
Tipologia:
2a Post-print versione editoriale / Version of Record
Licenza:
Non Pubblico - Accesso privato/ristretto
Dimensione
6.18 MB
Formato
Adobe PDF
|
6.18 MB | Adobe PDF | Visualizza/Apri Richiedi una copia |
22-06-11-COMPEL_submitted.pdf
accesso aperto
Tipologia:
2. Post-print / Author's Accepted Manuscript
Licenza:
Pubblico - Tutti i diritti riservati
Dimensione
6.2 MB
Formato
Adobe PDF
|
6.2 MB | Adobe PDF | Visualizza/Apri |
Pubblicazioni consigliate
I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.
https://hdl.handle.net/11583/2970345