When a single line to ground fault (SLGF) happens on the MV side of an HV/MV system, only a small portion of the fault current is injected into the ground by the ground grid of the faulty substation. In fact, the fault current is distributed between grounding electrodes and MV cables sheaths. In systems with isolated neutral or with resonant earthing, this may be sufficient to provide safety from electric shock. Experimental measurements were performed on a real MV distribution network: a real SLGF was made and fault currents were measured in the faulty substation and in four neighboring substations. In this paper, the problem of fault current distribution is introduced, the test system is described and the measurements results are presented.

Currents Distribution During a Fault in an MV Network: Methods and Measurements / Colella, Pietro; Napoli, Roberto; Pons, Enrico; Tommasini, Riccardo; Barresi, Antonino; Cafaro, Giuseppe; De Simone, Angelo; Di Silvestre, Maria Luisa; Martirano, Luigi; Montegiglio, Pasquale; Morozova, Elena; Parise, Giuseppe; Parise, Luigi; Riva Sanseverino, Eleonora; Torelli, Francesco; Tummolillo, Filomena; Valtorta, Giovanni; Zizzo, Gaetano. - In: IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS. - ISSN 0093-9994. - STAMPA. - 52:6(2016), pp. 4585-4593. [10.1109/TIA.2016.2600672]

Currents Distribution During a Fault in an MV Network: Methods and Measurements

COLELLA, PIETRO;NAPOLI, Roberto;PONS, ENRICO;TOMMASINI, Riccardo;
2016

Abstract

When a single line to ground fault (SLGF) happens on the MV side of an HV/MV system, only a small portion of the fault current is injected into the ground by the ground grid of the faulty substation. In fact, the fault current is distributed between grounding electrodes and MV cables sheaths. In systems with isolated neutral or with resonant earthing, this may be sufficient to provide safety from electric shock. Experimental measurements were performed on a real MV distribution network: a real SLGF was made and fault currents were measured in the faulty substation and in four neighboring substations. In this paper, the problem of fault current distribution is introduced, the test system is described and the measurements results are presented.
File in questo prodotto:
File Dimensione Formato  
Colella-PostPrint.pdf

accesso aperto

Descrizione: Postprint articolo
Tipologia: 2. Post-print / Author's Accepted Manuscript
Licenza: Pubblico - Tutti i diritti riservati
Dimensione 1.51 MB
Formato Adobe PDF
1.51 MB Adobe PDF Visualizza/Apri
07544530.pdf

accesso riservato

Descrizione: Articolo versione editoriale
Tipologia: 2a Post-print versione editoriale / Version of Record
Licenza: Non Pubblico - Accesso privato/ristretto
Dimensione 1.11 MB
Formato Adobe PDF
1.11 MB Adobe PDF   Visualizza/Apri   Richiedi una copia
Pubblicazioni consigliate

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11583/2650650