When a single line to ground fault (SLGF) happens on the MV side of an HV/MV system, only a small portion of the fault current is injected into the ground by the ground grid of the faulty substation. In fact, the fault current is distributed between grounding electrodes and MV cables sheaths. In systems with isolated neutral or with resonant earthing, this may be sufficient to provide safety from electric shock. Experimental measurements were performed on a real MV distribution network: a real SLGF was made and fault currents were measured in the faulty substation and in four neighboring substations. In this paper, the problem of fault current distribution is introduced, the test system is described and the measurements results are presented.
Currents Distribution During a Fault in an MV Network: Methods and Measurements / Colella, Pietro; Napoli, Roberto; Pons, Enrico; Tommasini, Riccardo; Barresi, Antonino; Cafaro, Giuseppe; De Simone, Angelo; Di Silvestre, Maria Luisa; Martirano, Luigi; Montegiglio, Pasquale; Morozova, Elena; Parise, Giuseppe; Parise, Luigi; Riva Sanseverino, Eleonora; Torelli, Francesco; Tummolillo, Filomena; Valtorta, Giovanni; Zizzo, Gaetano. - In: IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS. - ISSN 0093-9994. - STAMPA. - 52:6(2016), pp. 4585-4593. [10.1109/TIA.2016.2600672]
Currents Distribution During a Fault in an MV Network: Methods and Measurements
COLELLA, PIETRO;NAPOLI, Roberto;PONS, ENRICO;TOMMASINI, Riccardo;
2016
Abstract
When a single line to ground fault (SLGF) happens on the MV side of an HV/MV system, only a small portion of the fault current is injected into the ground by the ground grid of the faulty substation. In fact, the fault current is distributed between grounding electrodes and MV cables sheaths. In systems with isolated neutral or with resonant earthing, this may be sufficient to provide safety from electric shock. Experimental measurements were performed on a real MV distribution network: a real SLGF was made and fault currents were measured in the faulty substation and in four neighboring substations. In this paper, the problem of fault current distribution is introduced, the test system is described and the measurements results are presented.File | Dimensione | Formato | |
---|---|---|---|
Colella-PostPrint.pdf
accesso aperto
Descrizione: Postprint articolo
Tipologia:
2. Post-print / Author's Accepted Manuscript
Licenza:
Pubblico - Tutti i diritti riservati
Dimensione
1.51 MB
Formato
Adobe PDF
|
1.51 MB | Adobe PDF | Visualizza/Apri |
07544530.pdf
accesso riservato
Descrizione: Articolo versione editoriale
Tipologia:
2a Post-print versione editoriale / Version of Record
Licenza:
Non Pubblico - Accesso privato/ristretto
Dimensione
1.11 MB
Formato
Adobe PDF
|
1.11 MB | Adobe PDF | Visualizza/Apri Richiedi una copia |
Pubblicazioni consigliate
I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.
https://hdl.handle.net/11583/2650650