Protection of AC-side outgoing lines in three-stage solid-state transformers (SSTs) is challenging because control driven port currents undermine conventional current differential criteria, while overcurrent schemes are sensitive to transition resistance. This paper focuses on the phase-to-phase and three phase short-circuit faults, which are typically severe and require fast, reliable discrimination. Energy-differential protection offers a promising alternative; however, its direct application to SSTs is affected by substantial, control-dependent internal energy variations—mainly associated with submodule capacitors—which may delay internal-fault operation or trigger maloperation under external faults. This paper proposes an energy-differential protection scheme for three-stage SST AC-side outgoing lines with submodule-capacitor energy compensation. The proposed method suppresses the influence of internal energy dynamics without increasing setting margins or requiring additional measurement points. Its effectiveness is verified via MATLAB/Simulink simulations and RT-LAB real-time tests, demonstrating improved tolerance to transition resistance and enhanced noise immunity compared with existing methods.
An Energy Differential Protection Scheme for Three-Stage SST AC-Side Outgoing Lines with Submodule Capacitor Energy Compensation / Zhu, X., Li, Z., Zhou, N., Liao, J., Wang, Q., Huang, T.. - In: IEEE TRANSACTIONS ON POWER DELIVERY. - ISSN 0885-8977. - (2026). [10.1109/TPWRD.2026.3706143]
An Energy Differential Protection Scheme for Three-Stage SST AC-Side Outgoing Lines with Submodule Capacitor Energy Compensation
Huang T.
2026
Abstract
Protection of AC-side outgoing lines in three-stage solid-state transformers (SSTs) is challenging because control driven port currents undermine conventional current differential criteria, while overcurrent schemes are sensitive to transition resistance. This paper focuses on the phase-to-phase and three phase short-circuit faults, which are typically severe and require fast, reliable discrimination. Energy-differential protection offers a promising alternative; however, its direct application to SSTs is affected by substantial, control-dependent internal energy variations—mainly associated with submodule capacitors—which may delay internal-fault operation or trigger maloperation under external faults. This paper proposes an energy-differential protection scheme for three-stage SST AC-side outgoing lines with submodule-capacitor energy compensation. The proposed method suppresses the influence of internal energy dynamics without increasing setting margins or requiring additional measurement points. Its effectiveness is verified via MATLAB/Simulink simulations and RT-LAB real-time tests, demonstrating improved tolerance to transition resistance and enhanced noise immunity compared with existing methods.| File | Dimensione | Formato | |
|---|---|---|---|
|
Zhu-2026-An-Energy-Differential-Protection.pdf
accesso riservato
Descrizione: EarlyAccess
Tipologia:
2a Post-print versione editoriale / Version of Record
Licenza:
Non Pubblico - Accesso privato/ristretto
Dimensione
2.51 MB
Formato
Adobe PDF
|
2.51 MB | Adobe PDF | Visualizza/Apri Richiedi una copia |
|
main.pdf
embargo fino al 23/06/2028
Descrizione: AAM
Tipologia:
2. Post-print / Author's Accepted Manuscript
Licenza:
Pubblico - Tutti i diritti riservati
Dimensione
7.43 MB
Formato
Adobe PDF
|
7.43 MB | Adobe PDF | Visualizza/Apri Richiedi una copia |
Pubblicazioni consigliate
I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.
https://hdl.handle.net/11583/3017572