Natural ventilation is key for reducing energy demand and ensuring indoor air quality. We study the deterministic and stochastic dynamics of a naturally ventilated system where a room with a steady buoyancy source connects to an unforced atrium (an arrangement representative of many real buildings). The buoyant fluid accumulates at the ceiling of both spaces. A stratification arises, inducing the stack effect which drives the ventilation of the system. We consider the occurrence of an opposing wind. Firstly, a constant wind is imposed, and the steady states are analysed for different atrium geometries. It is known that when no external wind occurs the atrium may either enhance or worsen the ventilation of the room depending on its geometry. We find that for any geometry the atrium enhances the ventilation for a wind velocity large enough. Secondly, stochastic fluctuations are introduced in the wind velocity. These induce a ‘noise-induced transition’: the mean position of the interface between warm and cold layers lies below that observed under constant wind. This phenomenon was already known for single-room systems; however, we find that the room-atrium system is less sensitive to this effect and to variations in the coefficient of variation of wind velocity

Natural ventilation of a room-atrium building with opposing wind: a deterministic and stochastic analysis / Di Renzo, Teresa; Marro, Massimo; Ridolfi, Luca; Salizzoni, Pietro Stefano; Vesipa, Riccardo. - In: ENVIRONMENTAL FLUID MECHANICS. - ISSN 1567-7419. - ELETTRONICO. - 26:5(2026), pp. 1-29. [10.1007/s10652-025-10071-z]

Natural ventilation of a room-atrium building with opposing wind: a deterministic and stochastic analysis

Teresa, Di Renzo;Massimo, Marro;Luca, Ridolfi;Pietro, Salizzoni;Riccardo, Vesipa
2026

Abstract

Natural ventilation is key for reducing energy demand and ensuring indoor air quality. We study the deterministic and stochastic dynamics of a naturally ventilated system where a room with a steady buoyancy source connects to an unforced atrium (an arrangement representative of many real buildings). The buoyant fluid accumulates at the ceiling of both spaces. A stratification arises, inducing the stack effect which drives the ventilation of the system. We consider the occurrence of an opposing wind. Firstly, a constant wind is imposed, and the steady states are analysed for different atrium geometries. It is known that when no external wind occurs the atrium may either enhance or worsen the ventilation of the room depending on its geometry. We find that for any geometry the atrium enhances the ventilation for a wind velocity large enough. Secondly, stochastic fluctuations are introduced in the wind velocity. These induce a ‘noise-induced transition’: the mean position of the interface between warm and cold layers lies below that observed under constant wind. This phenomenon was already known for single-room systems; however, we find that the room-atrium system is less sensitive to this effect and to variations in the coefficient of variation of wind velocity
File in questo prodotto:
File Dimensione Formato  
REVISED_natural_ventilation_room_atrium_building.pdf

embargo fino al 26/12/2026

Descrizione: Accepted manuscript
Tipologia: 2. Post-print / Author's Accepted Manuscript
Licenza: Pubblico - Tutti i diritti riservati
Dimensione 2.25 MB
Formato Adobe PDF
2.25 MB Adobe PDF   Visualizza/Apri   Richiedi una copia
natural_ventilation_of_a_room-atrium_building.pdf

accesso riservato

Descrizione: Published manuscript
Tipologia: 2a Post-print versione editoriale / Version of Record
Licenza: Non Pubblico - Accesso privato/ristretto
Dimensione 6.04 MB
Formato Adobe PDF
6.04 MB Adobe PDF   Visualizza/Apri   Richiedi una copia
Pubblicazioni consigliate

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11583/3006304