The second operating phase of the W7X stellarator, with an expanded set of plasma-facing components, includes the test of divertor tiles with a continuous heat load reaching 10 MW/ m2. The divertor tiles are cooled by subcooled water. Here a novel cooling concept, based on a network of parallel arrays of micro-channels (MC) with sub-millimetre dimensions, is investigated on a 0.1 m x 0.1 m tile, realizable by Additive Manufacturing. Detailed CFD simulations of the mock-up are performed to check the cooling uniformity using a multi-scale approach, aiming at limiting the dimension of the computational grid without a major loss of accuracy. First, the detailed hydraulic and thermal characterization on a sub-domain with of a small group of MC is performed. Then, the block of MC is substituted with an equivalent porous strip (PS), calibrating the hydraulic and thermal characteristics of the porous medium. The model is verified on an array of MCs or PSs connected to the same manifolds, showing the capability to reproduce the pressure drop and temperature increase with maximum errors of 1.05% and similar to 20% in nominal conditions, respectively. The numerical model of the entire tile equipped with PSs is then reliably adopted to evaluate the thermal-hydraulic performance of the cooling device.

A multi-scale hybrid approach to the modelling and design of a novel micro-channel cooling structure for the W7X divertor / Ebadi, H; Carrone, F; Difonzo, R; Fellinger, J; Laqua, Hp; Schneider, N; Savoldi, L. - In: CASE STUDIES IN THERMAL ENGINEERING. - ISSN 2214-157X. - 42:(2023), p. 102734. [10.1016/j.csite.2023.102734]

A multi-scale hybrid approach to the modelling and design of a novel micro-channel cooling structure for the W7X divertor

Ebadi, H;Carrone, F;Difonzo, R;Savoldi, L
2023

Abstract

The second operating phase of the W7X stellarator, with an expanded set of plasma-facing components, includes the test of divertor tiles with a continuous heat load reaching 10 MW/ m2. The divertor tiles are cooled by subcooled water. Here a novel cooling concept, based on a network of parallel arrays of micro-channels (MC) with sub-millimetre dimensions, is investigated on a 0.1 m x 0.1 m tile, realizable by Additive Manufacturing. Detailed CFD simulations of the mock-up are performed to check the cooling uniformity using a multi-scale approach, aiming at limiting the dimension of the computational grid without a major loss of accuracy. First, the detailed hydraulic and thermal characterization on a sub-domain with of a small group of MC is performed. Then, the block of MC is substituted with an equivalent porous strip (PS), calibrating the hydraulic and thermal characteristics of the porous medium. The model is verified on an array of MCs or PSs connected to the same manifolds, showing the capability to reproduce the pressure drop and temperature increase with maximum errors of 1.05% and similar to 20% in nominal conditions, respectively. The numerical model of the entire tile equipped with PSs is then reliably adopted to evaluate the thermal-hydraulic performance of the cooling device.
File in questo prodotto:
File Dimensione Formato  
1-s2.0-S2214157X23000400-main (1).pdf

accesso aperto

Tipologia: 2a Post-print versione editoriale / Version of Record
Licenza: Creative commons
Dimensione 2.76 MB
Formato Adobe PDF
2.76 MB Adobe PDF Visualizza/Apri
Pubblicazioni consigliate

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11583/2976672