This paper applies a novel and fast modelling approach to simulate tunnel ventilation flows during fires. The complexity and high cost of full CFD models and the inaccuracies of simplistic zone or analytical models are avoided by efficiently combining mono-dimensional (1D) and CFD (3D) modelling techniques. A simple 1D network approach is used to model tunnel regions where the flow is fully developed (far field), and a detailed CFD representation is used where flow conditions require 3D resolution (near field). This multi-scale method has previously been applied to simulate tunnel ventilation systems including jet fans, vertical shafts and portals (Colella et al., Build Environ 44(12): 2357-2367, 2009) and it is applied here to include the effect of fire. Both direct and indirect coupling strategies are investigated and compared for steady state conditions. The methodology has been applied to a modern tunnel of 7 m diameter and 1.2 km in length. Different fire scenarios ranging from 10 MW to 100 MW are investigated with a variable number of operating jet fans. Comparison of cold flow cases with fire cases provides a quantification of the fire throttling effect, which is seen to be large and to reduce the flow by more than 30% for a 100 MW fire. Emphasis has been given to the discussion of the different coupling procedures and the control of the numerical error. Compared to the full CFD solution, the maximum flow field error can be reduced to less than few percents, but providing a reduction of two orders of magnitude in computational time. The much lower computational cost is of great engineering value, especially for parametric and sensitivity studies required in the design or assessment of ventilation and fire safety systems

A Novel Multiscale Methodology forSimulating Tunnel Ventilation Flows duringFire / Colella, Francesco; Rein, G; Borchiellini, Romano; Torero, J. L.. - In: FIRE TECHNOLOGY. - ISSN 0015-2684. - 47:1(2011), pp. 221-253. [10.1007/s10694-010-0144-2]

A Novel Multiscale Methodology forSimulating Tunnel Ventilation Flows duringFire

COLELLA, FRANCESCO;BORCHIELLINI, Romano;
2011

Abstract

This paper applies a novel and fast modelling approach to simulate tunnel ventilation flows during fires. The complexity and high cost of full CFD models and the inaccuracies of simplistic zone or analytical models are avoided by efficiently combining mono-dimensional (1D) and CFD (3D) modelling techniques. A simple 1D network approach is used to model tunnel regions where the flow is fully developed (far field), and a detailed CFD representation is used where flow conditions require 3D resolution (near field). This multi-scale method has previously been applied to simulate tunnel ventilation systems including jet fans, vertical shafts and portals (Colella et al., Build Environ 44(12): 2357-2367, 2009) and it is applied here to include the effect of fire. Both direct and indirect coupling strategies are investigated and compared for steady state conditions. The methodology has been applied to a modern tunnel of 7 m diameter and 1.2 km in length. Different fire scenarios ranging from 10 MW to 100 MW are investigated with a variable number of operating jet fans. Comparison of cold flow cases with fire cases provides a quantification of the fire throttling effect, which is seen to be large and to reduce the flow by more than 30% for a 100 MW fire. Emphasis has been given to the discussion of the different coupling procedures and the control of the numerical error. Compared to the full CFD solution, the maximum flow field error can be reduced to less than few percents, but providing a reduction of two orders of magnitude in computational time. The much lower computational cost is of great engineering value, especially for parametric and sensitivity studies required in the design or assessment of ventilation and fire safety systems
File in questo prodotto:
Non ci sono file associati a questo prodotto.
Pubblicazioni consigliate

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11583/2288191
 Attenzione

Attenzione! I dati visualizzati non sono stati sottoposti a validazione da parte dell'ateneo